Experimental heat transfer and isothermal pressure drop data for single-phase water flows in a plate heat exchanger (PHE) with chevron plates are presented. In a single-pass U-type counterflow PHE, three different chevron plate arrangements are considered: two symmetric plate arrangements with β = 30 deg/30 deg and 60 deg/60 deg, and one mixed-plate arrangement with β = 30 deg/60 deg. For water (2 < Pr < 6) flow rates in the 600 < Re < 104 regime, data for Nu and f are presented. The results show significant effects of both the chevron angle β and surface area enlargement factor φ. As β increases, and compared to a flat-plate pack, up to two to five times higher Nu are obtained; the concomitant f, however, are 13 to 44 times higher. Increasing φ also has a similar, though smaller effect. Based on experimental data for Re a 7000 and 30 deg ≤ β ≤ 60 deg, predictive correlations of the form Nu = C1,(β) D1(φ) Rep1(β)Pr1/3(μ/μw)0.14 and f = C2(β) D2(φ) Rep2(β) are devised. Finally, at constant pumping power, and depending upon Re, β, and φ, the heat transfer is found to be enhanced by up to 2.8 times that in an equivalent flat-plate channel.
Skip Nav Destination
Article navigation
Research Papers
Experimental Study of Turbulent Flow Heat Transfer and Pressure Drop in a Plate Heat Exchanger With Chevron Plates
A. Muley,
A. Muley
Department of Mechanical, Industrial and Nuclear Engineering, University of Cincinnati, Cincinnati, OH 45221-0072
Search for other works by this author on:
R. M. Manglik
R. M. Manglik
Department of Mechanical, Industrial and Nuclear Engineering, University of Cincinnati, Cincinnati, OH 45221-0072
Search for other works by this author on:
A. Muley
Department of Mechanical, Industrial and Nuclear Engineering, University of Cincinnati, Cincinnati, OH 45221-0072
R. M. Manglik
Department of Mechanical, Industrial and Nuclear Engineering, University of Cincinnati, Cincinnati, OH 45221-0072
J. Heat Transfer. Feb 1999, 121(1): 110-117 (8 pages)
Published Online: February 1, 1999
Article history
Received:
September 12, 1997
Revised:
October 7, 1998
Online:
December 5, 2007
Citation
Muley, A., and Manglik, R. M. (February 1, 1999). "Experimental Study of Turbulent Flow Heat Transfer and Pressure Drop in a Plate Heat Exchanger With Chevron Plates." ASME. J. Heat Transfer. February 1999; 121(1): 110–117. https://doi.org/10.1115/1.2825923
Download citation file:
Get Email Alerts
Cited By
Thermal Anisotropy and Heat Flux Deviation Degree of Composites
J. Heat Mass Transfer
Reviewer's Recognition
J. Heat Mass Transfer (April 2025)
Related Articles
Heat Transfer in Crossflow Over Cylinders Between Two Parallel Plates
J. Heat Transfer (August,1992)
Heat Transfer and Pressure Drop Characteristics of an Assembly of Partially Segmented Plates
J. Heat Transfer (February,1989)
Heat Transfer-Friction Characteristic Comparison in Rectangular Ducts With Slit and Solid Ribs Mounted on One Wall
J. Heat Transfer (August,1998)
Heat Exchange Effectiveness and Pressure Drop for Air Flow Through Perforated Plates With and Without Crosswind
J. Heat Transfer (May,1994)
Related Proceedings Papers
Related Chapters
Heat Transfer and Pressure Drop Correlations for Compact Heat Exchangers with Multi-Region Louver Fins
Inaugural US-EU-China Thermophysics Conference-Renewable Energy 2009 (UECTC 2009 Proceedings)
Heat Transfer in a Heat Exchanger
Everyday Heat Transfer Problems: Sensitivities to Governing Variables
Hydrodynamic Mass, Natural Frequencies and Mode Shapes
Flow-Induced Vibration Handbook for Nuclear and Process Equipment